Come From?
Conversions
Requirements of a Balanced 3-Phase Set
Following are the requirements that must be satisified in order for a set of 3 sinusoidal variables (usually voltages or currents) to be a "balanced 3-phase set"
In terms of the time domain, a set of balance 3-phase voltages has the following general form.
Vm cos (
t +
)
Vm cos (
t +
- 120o )
Vm cos (
t +
- 240o )
=
Vm cos (
t +
+120o )
Figure 1 below illustrates the balanced 3-phase voltages in time domain.

Figure 1: Balanced 3-Phase Variables in Time Domain
m
- 120o
- 240o
= Vm
+120o
Thus,
-120o) , and
Vc = Va (1
+120o)

Figure 2: Balanced 3-Phase Phasors
Having a balanced circuit allows for simplified analysis of the 3-phase circuit. In fact, if the circuit is balanced, we can solve for the voltages, currents, and powers, etc. in one phase using circuit analysis. The values of the corresponding variables in the other two phases can be found using some basic equations. This type of solution is accomplished using a "one-line diagram", which will be discussed later. If the circuit is not balanced, all three phases should be analyzed in detail.
Figure 3 illustrates a balanced 3-phase circuit and some of the naming conventions to be used in this course

Figure 3: A Balanced 3-Phase Circuit
.
Come From?
Vab = Va - Vb
= Vm
- Vm
- 120o
Now, without loss of generality, let
= 0o
thus, Va = Vm
0o,
and Vb = Vm
-120o, so
Vab
= Vm
0o
- Vm
- 120o
= Vm (1 - 1
- 120o )
= Vm (1 - (cos 120o - j sin 120o))
= Vm (1 - (-1/2) + j (
/ 2 ) )
= Vm (3 / 2) + j (
/ 2 ))
Converting to polar form,
Vab = Vm Sqrt[ (3/2)2 + (
/ 2)2 ]
tan-1 {(
/ 2) / (3/2) }
= Vm Sqrt[ 9/4 + 3/4 ]
tan-1 {1/
}
= Vm
tan-1 {(1 / 2) / (
/2) }
= Vm
tan-1 {(sin 30o) / (cos 30o) }
= Vm
tan-1 {tan 30o }
= Vm
30o
Thus we have the general equation (for abc sequence anyway)
30o
Ia = IAB - ICA
This time choose Ia to be the phasor reference (at 0o). The final result is:
-30o
Since Vab is longer, we know . . . .
|Vab| =
|Va| ,
and since Vab is ahead of Va, we know that, . . . . (the angle of Vab) = (the angle of Va) + 30o

Figure 4: Graphical Voltage Relationship
Since Ia is longer, we know
|Ia| =
|Iab| ,
and since Ia is behind Iab, we know that,
(the angle of Ia) = (the angle of Iab) - 30o
Figure 5: Graphical Current Relationship

Wyes and Deltas
A summary of the characteristics of the two types of 3-phase circuit connections are given
below.
| ____ | connection | |
| each phase is connected between a line and the neutral | each phase is connected between two lines | |
| ![]() | |
Circuit | ||
| Phase voltages = Line to neutral voltages (Va, etc.) Phase currents = Line currents (Ia, etc.)
| Phase voltages = Line voltages (Vab, etc.) Phase currents = currents from line to line (Iab, etc.)
|
Conversions
| ____ | ||
| ![]() | |
Source | ||
30o) | 30o) |
Similarly, the two loads given below are the same in terms of the resulting power, line currents and line voltages and can usually be substituted as desired. Note that the Y connection is the one needed for the one-line diagram!
| ____ | ||
| ![]() | |
Impedance Load |
The One-Line Diagram
If the circuit is balanced, all corresponding sets of 3-phase voltages and currents are
balanced, and the neutral current will be zero.
IN = Ia + Ib + Ic
Why must this be so? Because the sum of a balanced set of 3-phase variables is equal to zero. This can be verified mathematically using the definition, or visually by considering using vector addition to add the balanced set in Figure 5.
Because the neutral current is zero, this means that if the neutral in the load is connected to the neutral in the source, no current will flow. Thus, the voltage at each of the neutrals must be the same. This means they can be considered to be the same point.
Now consider the circuit of Figure 12. In general, any circuit with a source, load, and line configuration can be converted to a circuit of this type by replacing any Delta -connected sources or loads with the equivalent Wye connected sources or loads.

Figure 12: Completely Y-Connected Circuit Including Neutral

Figure 13: ReDrawn All-Y Circuit
Ia = Va / ( Zline + ZY) , Ib = Vb / ( Zline + ZY) , and Ic = Vc / ( Zline + ZY)
Notice that these equations are VERY similar.
Recall that in balanced set of variables, once we know one variable, the other two can be found by simply adding and subtracting 120o. Thus, we only need to consider and solve one loop of Figure 13 --- this is the one-line diagram!
Figure 14 shows the one-line diagram for the circuit of Figure 13. Usually the one line that is considered is the "a" phase. The "b" phase quantities are then found by subtracting 120o, and the "c" phase quantities are found by adding 120o.

Figure 14: The One-Line Diagram
) power of a circuit is simply the sum of the power in the three
individual phases. Thus for a Wye circuit, the equation is
S3
= Sa + Sb + Sc
and for a Delta circuit, the equation is
S3
= Sab + Sbc + Sca
Another adavantage of having a balanced circuit is that each phase has the same power. That is,
S
= Sab = Sbc = Sca = Sa = Sb = Sc
so that,
S3
= 3 S
= 3 Sab = 3 Sa
Just in case you didn't know, right now you should be thinking "This is very cool!"
The single phase power can be found using either
S
= Va Ia*
or
S
= Vab Iab*
We can do some interesting rearrangements to get the power in terms of the line voltage (Vab) and line current (Ia) only.
S
= Va Ia*
= |Va| | Ia| 
= {|Vab| /
}| Ia| 
= S
Thus,
S3
= 3 S
= 3 {|Vab| /
}| Ia| 
=
|Vab| | Ia| 
's and
S3
have the same power factor (pf) and thus the
same power factor angle = impedance angle =
.
-120o) , and
+120o)
= Sa + Sb + Sc
= Sab + Sbc + Sca
= 3 S
= Va Ia*
= Vab Iab*
30o
-30o
, P3
, or Q3
In general, a unbalanced three-phase circuit requires that you draw the complete circuit including all 3-phase and single-phase loads and perform a circuit analysis of the whole thing. Normal methods such as "meshes" or "node voltages" may be used. If you have the simple case in which a balanced 3-phase load is connected directly to a source and a single phase load is connected in parallel to the same source, you may calculate the currents in the balanced load using a one-line method. The single phase current is calculated separately and then individual line currents can be found by summing the currents at certain nodes in the system.
Remember any circuit that does not have all loads with the same
impedance in all three branches is an unbalanced circuit.
Wattmeters
The schematic for a wattmeter is given in Figure 15 below.
Note that in order to measure power, we need to measure a
current and a voltage. The wattmeter doesn't care which
current or which voltage you use. It will give you a reading
regardless of whether or not it means anything. It is up
to the user (you) to make sure the meter is sensing the
correct voltage and current to give a meaningful measurement!

Figure 15: The Basic Wattmeter
V -
I )
Under balanced conditions and conditions in which there are only three wires in the system, we can measure the power in all three phases of a load (or source) by using only two meters. This is called the "Two Wattmeter Method."
This method is quite convenient when all you have access to are
the three wires going into a three-phase motor (for example).
You want to measure P3
, where
do you connect your meter?
connect the positive terminals of the voltage coils to the same two phases (where you're measuring the current)
connect both of the negative voltage terminals to the third phase.
Figures 16 and 17 below show two possible connections with phases "b" and "c" respectively, used as the voltage reference. Note that the "plus-minus" symbol marks the positive voltage terminal & the negative terminal is generally unmarked.

Figure 16: Two Wattmeter Connection with "b" as Reference

Figure 17: Two Wattmeter Connection with "c" as Reference
Vab
-
Ia )
W2 = |Ic| |Vcb|
cos (
Vcb
-
Ic )
Vac
-
Ia )
W2 = |Ib| |Vbc|
cos (
Vbc
-
Ib )
= W1 + W2
similarly, for the balanced condition, the magnitude three phase
reactive power can be found using . . .
|Q3
| =
|W1 - W2|
the sign of Q may vary depending on how the wattmeters are connected. So, it is generally safer to determine the sign using other means.
September 18, 1997