Objectives
Background
Three-phase squirrel cage induction motors comprise the vast majority of all electric motors made in larger sizes, say 5 hp or more. They are rugged and reliable. It is not uncommon for such motors to be in daily use for more than half a century, with the only maintenance being a new set of bearings every ten years or so. They do not produce sparks like DC motors do, so they can be used in hazardous environments like oil refineries and grain elevators. They are efficient, with efficiencies around 90% for a few hp, increasing to perhaps 98% for the very large sizes. They are even relatively quiet compared with single-phase motors. You should notice the difference in noise level between this Block and the later one dealing with single-phase motors. A large fraction of these motors are specified by mechanical engineers for use in grinding, pumping, and blowing operations, so mechanical engineers need to know something about them.
The electrical input of the three-phase induction motor is modeled in Fig. 1. There are three windings on the stator (the stationary part of the motor). They are located 120o apart in space around the perimeter of the stator. In Fig. 1 they are shown connected in wye, with the common or neutral point available. The windings can also be connected in delta, which of course does not have a neutral point. In practice, the neutral is not brought out of the motor even if it is wired in wye, so it is impossible to tell which way a motor is wired by an external examination. It does not make any difference in performance so probably only a few people in the manufacturing facility actually know which wiring technique was used. We will analyze the motor using the wye convention, with the analysis being valid for wye connected loads in general.
The motor nameplate always lists the line-to-line voltage VL and the
line current IL, but analysis usually is performed using the line-to-
neutral or phase voltage VP. That is, we do single-phase analysis
because it is easier and multiply by 3 or
to get the desired
three-phase quantities. The phase current IP will lag the phase voltage
VP by an angle
. The power factor is defined as
..........(1)
In the following set of equations, voltages and currents will be taken as
their magnitudes, with all phase relationships treated by a function of
. The average power supplied to one phase of the motor is
VPIPcos
. The total average power supplied to the motor is
then
..........(2)
Since VL =
VP and IP = IL, we can also write (2) as
VL IL
cos
..........(3)We are also interested in two other quantities, the apparent power S and the reactive power Q, defined as
VL IL..........(4)
=
VL IL
sin
..........(5)Note that
In this Block we introduce two additional measuring instruments, the
wattmeter, which measures P, and the varmeter, which measures Q.
The
apparent power is obtained by just multiplying the voltmeter and ammeter
readings. We therefore have plenty of information to calculate the power
factor and the angle
. In fact we have enough information to
perform some internal tests for consistent data. We can evaluate the left
portion of (6) from the voltmeter and ammeter, and the right portion
from the wattmeter and varmeter, and if the two sides do not agree, then
something is wrong with our reading of at least one of the instruments. We
will ask you to do some of these consistency checks in this experiment.
All three powers are dimensionally the same, but we write the units differently to remind us of the quantities we are dealing with. When we see VA, we are reminded of apparent power. Real or average power is expressed in Watts. VAR stands for Volt Ampere Reactive and indicates reactive power. The SI purist is a bit unhappy about using three different labels for something dimensionally the same, but this seems to be one of those places where clarity of communication is more important than dogmatic adherence to a set of rules.
The mechanical output power of the motor is given by
m ..........(8)
where Pout is in W, T is in Nm, and
m is in rad/s.
In this lab we actually measure the speed with a Strobotac in rpm, and
torque with a dynamometer in inch pounds, so the equivalent formula is
..........(9)where Pout is still in W, T is in inch pounds, and n is in rpm. The efficiency of the motor is then given by
..........(10)The stator field rotates at a synchronous speed
..........(11)where f is the frequency in Hz and p is the number of poles. A four pole machine operating on a line voltage at 60 Hz would have a synchronous speed of 1800 rpm. The actual speed of the motor will be less than the synchronous speed by an amount proportional to the slip s, where
..........(12)Slip gets larger as the mechanical load increases. Slip will be near zero when the motor is unloaded, and will be in the range of 3 to 6% at full load. Higher efficiency motors have smaller slip. If you are comparing two motors at the same power rating, and one has a rated speed of 1745 rpm and the other has a rated speed of 1755 rpm, you are safe in assuming that the 1755 rpm motor has the higher efficiency.
One of the few disadvantages of induction motors is their lagging power factor. Transformers are always specified in terms of apparent power, so a larger transformer is required to supply a given amount of real power when the power factor is low. The larger current flow also increases the copper losses for a given amount of real power. Utility companies can therefore reduce both capital and operating costs if the power factor is increased to a value close to unity. Utilities will often impose a power factor penalty on manufacturing plants if the power factor drops below perhaps 0.9. The standard way for a manufacturing plant to improve its power factor is to add a capacitor bank, since the capacitive VARs will counteract the inductive VARs of the motors.
The reactive power supplied by a capacitor C at voltage V is
..........(13)Multiply this value by 3 to account for the three capacitors in a capacitor bank.
Example: An industrial load consists of 150 kVA (input) of induction motors operating at 0.6 pf lag. What is the kVAR rating of the capacitor bank necessary to raise the power factor to 0.9 lag?
The key to doing power factor correction problems is to remember that the real power remains constant. Capacitors draw only reactive power, not real power. The real power in this case is
The reactive power being supplied to the motors is
The apparent power with the capacitors in place will be
The angle is
= arccos(0.9) = 25.84o The total reactive power supplied to the combination is
The difference must be supplied by the capacitors.
Note that it will not be practical to `fine tune' the capacitor bank to get exactly -76.41 kVAR. Capacitor banks are sold in nominal values like -75 and -90 kVAR. If you wanted to make sure the power factor would be at least 0.9, then you would specify the next larger size. If that happened to be -90 kVAR for this example, the total reactive power becomes 30 kVAR, with a new apparent power
The new power factor is
Discussion and Calculations
a) What is the necessary kVAR rating of the capacitor bank?
b) What is the current into the motor ILm?
c) What is the current supplied by the utility IL?
d) What is the current in each capacitor?
e) What is the necessary value of each capacitor in µF?
resistor?
The Fluke probe is diode protected against open circuits on the output, but
assume for a moment that it is not. If the load resistance were changed
from 10
to 1 Mega
, what would the rms output voltage be for 1A
input? Why do you suppose that people insist on keeping current
transformers short circuited when not connected to a low impedance load?
Instructional Activity in Class
Check the calibration on your current transformer by noting the peak
voltage into the oscilloscope for an rms current through the 0-5 AC AMPS
meter of about 2A. Do not exceed a line-to-line voltage of 120 volts. Set
the oscilloscope in the storage mode to record starting current from the
current transformer. Adjust the three-phase variable autotransformer for
60 volts line-to-line. Open and close the three-phase breaker to record
starting current. Record in your notebook the peak amplitude of voltage
across the 10
resistor, the corresponding peak current, and the
number of cycles required to reach steady state. Repeat for line-to-line
voltages of 90 and 120 volts.
Turn on the AC power to the small variable autotransformer on the dynamometer. Record data for five settings of this variable autotransformer: 0 lb-in (no load), 3 lb-in, 6 lb-in, 8 lb-in, and full load. Turn the three-phase variable autotransformer up so the motor is running with the line-to-line voltage set at 120 V. For each of the four settings, record the wattmeter and varmeter readings, rpm, line current, and the dynamometer torque. Don't forget to multiply the wattmeter and varmeter readings by the appropriate constants. The constants are given by the dials near the meters. Leave the circuit connected until Lab Activity 8 is completed.
V I and
, the power
factor, the slip, the power delivered to the dynamometer, and the motor
efficiency, for each of the four load settings in Lab Activity 7. Do the two
methods of computing apparent power yield consistent results?
Conclusion